CIRCUIT CONNECTIONS
Circuit Type
Circuit Function
SLC loop
Connects to
(power-limited)
Addressable
Devices
CLIP MODE
LITESPEED
MODE
ACS-BUS
Connects to
(EIA-485)
annunciator
(power-limited)
modules
ANN-BUS
Connects to
(EIA-485)
annunciator
(power-limited)
modules
EIA-232
connects to
(power-limited)
remote PC
computer
MMF-300 and
Initiating Device
MMF-301
Circuit: Contact
(power-limited)
Closure
MMF-302
Initiating Device
(power-limited)
Circuit: Two-wire
Modules
CMF-300
Notification
(power-limited)
Appliance
Circuit
Remote Sync
Provides strobe
Output
and normal sync
for remote NAC
power supplies
1 When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Recommended
Wire Type and
Max. Distance
Limitations
Feet (meters)
Twisted, shielded pair
10,000 (3,000 m)
40 ohms maximum per
8,000 (2,400 m)
length of Style 6 and 7
4,875 (1,450 m)
loops. 40 ohms per
3,225 (980 m)
branch maximum for
Style 4 loops
Twisted, unshielded pair
10,000 (3,000 m)
40 ohms maximum per
8,000 (2,400 m)
length of Style 6 and 7
4,875 (1,450 m)
loops. 40 ohms per
3,225 (980 m)
branch maximum for
Style 4 loops
Untwisted, unshielded
3,000 (900 m)
1
pair
Twisted pair with a
6,000 (1,800 m)
characteristic impedance
of 120 ohms
Twisted pair
6,000 (1,800 m)
Twisted, shielded pair
50 (15 m)
Maximum loop wire
2,500 (760 m)
resistance is 1500 ohms
No more than a 2.4 volt
2,500 (760 m)
drop allowed at end of
circuit. Maximum loop
wire resistance is 25
ohms
In alarm, no more than a
Distance limitation
1.2 volt drop allowed at
set by 1.2 volt
end of circuit
maximum line
drop
Untwisted, unshielded
Distance set by
pair wire
295 ohm
resistance
limitation
Table E.1 FACP Wire Specifications
WIRE REQUIREMENTS
Wire Gauge and Compatible Brands
12 AWG (3.25 mm
Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm
Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec
NP713110VNQ-S
18 AWG (0.75 mm
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec
NP714110VNQ-S
12 AWG (3.25 mm
6020UL, Genesis WG-4315 & WG-4515
14 AWG (2.00 mm
6120UL, Genesis WG-4313 & WG-4513
16 AWG (1.30 mm
6220UL, Genesis WG-4311 & WG-4511
18 AWG (0.75 mm
6320UL, Genesis WG-4306 & WG-4506
12-18 AWG (3.25 - 0.75 mm
wire
12 AWG (0.75 mm
Refer to "ANN-BUS Wiring" on page 23 for
information on device wiring
18 AWG (0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
Wire Requirements
2
): Genesis 4410,
2
):Genesis 4408 & 4608
2
): Genesis 4406 & 4606
2
): Genesis 4402 & 4602
2
): Belden 5020UL &
2
):Belden 5120UL &
2
): Belden 5220UL &
2
): Belden 5320UL &
2
) using listed
2
)
2
) minimum
2
)
2
)
2
)
2
)
209