Drift Compensation; Maintenance Alert - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Read Status
If the addressable smoke detector's Chamber reading is not within the acceptable range, clean the
detector and check the Chamber value again. If the reading is still not within the acceptable range,
immediately replace the detector.

Drift Compensation

Drift compensation uses software algorithms that identify and compensate for long-term changes in
the data readings from each addressable smoke detector. These long-term changes in detector data
readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift
compensation performs the following functions:
Samples photoelectric smoke detectors every 6 seconds and ionization smoke detectors every 3
seconds
Allows a smoke detector to retain its original ability to detect actual smoke and resist false
alarms, even as dirt and dust accumulate
Reduces maintenance requirements by allowing the control panel to automatically perform the
periodic sensitivity measurements required by NFPA Standard 72
The FACP software also provides filters to remove transient noise signals, usually caused by
electrical interference.

Maintenance Alert

The software determines when the drift compensation for a detector reaches an unacceptable level
that can compromise detector performance. When a detector reaches an unacceptable level, the
control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance
alert:
Maintenance Level:
Low Chamber Value
Maintenance Alert
Maintenance Urgent
Figure 4.1 illustrates a graphic representation of the maintenance levels:
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
FACP Status Displays:
INVREP
DIRTY1
DIRTY2
Table 4.1 Maintenance Alert Levels
Maintenance
Urgent
Acceptable
Low Chamber
Reading
Figure 4.1 Diagram of Maintenance Levels
Indicates:
A hardware problem in the detector
Dust accumulation that is near but below the allowed
limit. DIRTY 1 indicates the need for maintenance
before the performance of the detector is
compromised
Dust accumulation above the allowed limit.
DIRTY
Maintenance
Alert
Range
LOW
VALUE
Operating Instructions