Master Programming Level
If the selected address corresponds to a monitor module, a screen displaying information about the
module with the selected address will be displayed as illustrated in the following:

Enable/Disable Module

To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen
#2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled
No is selected, the module will not be polled by the control panel, preventing the module from
reporting alarms and troubles to the panel. The control panel will indicate a system trouble
condition and the Disable LED with turn on if any devices are disabled.
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
NORMAL MONITOR
<ADJ><NOUN>
EDIT MONITOR
1=ENABLED
2=TYPE
MONITOR
Edit Monitor Screen #2
EDIT MONITOR
1=PRE-SIGNAL
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
Edit Monitor Screen #5
ZNNN
1M012
1M012
YES
1M012
NO
1M012
YES
1M012
Programming