Maintenance Programming Level
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be
displayed:
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit
day and four digit year. The cursor will move one position to the right after each entry. When the
fourth digit of the year has been entered, the display will return to the Time and Date Screen which
will show the new date.
3.7.6 Zone Setup
PROGRAMMING
Pressing 3 while viewing Maintenance Screen #2 will display the following screen:
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
Pressing 1 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number
(00 - 99). After the second digit is entered, the zone will be enabled and the cursor will return to the
original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to
the previous screen.
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
ENTER DATE
MONTH DAY YEAR
01-01-2006
Date Screen
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen
ZONE TO ENABLE
Z
Enable Screen
Programming
155