2=Zones - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Operating Instructions
4.22.2 Zones
READ STATUS
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
1=SYSTEM POINT

2=ZONES

3=POWER
Read Status Screen #1
From the preceding screens, the control panel operator can view:
172
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
Pre-Signal Yes/No (for detectors and monitor modules)
Zone Assignments (five maximum)
Chamber Value
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
1=SPECIAL PURPOSE
2=ZONE TYPE
3=ZONE MESSAGE
Zones Installed - all software zones programmed into the system (99 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98
reserved for Pre-signal and 99 reserved for Two Stage
Zone Type - the Type assigned to each installed zone (default is Alarm)
Zone Message - the Message assigned to each installed zone
ZONES
Zones Screen #1
ZONES
Zones Screen #2
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Read Status