Accessories
A standard USB cable with male-A to male-B connectors, which must be purchased separately, is
required for local connection of the PC to the USB port J12 on the FACP main circuit board.
Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to "Remote Site Upload/Download" on page 186). Remote interrogation
of panel programming, history logs, detector status, etc., is possible without enabling the remote
download option.
1.7.2 DP-9692 Dress Panel
An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Cana-
dian installations). The dress panel restricts access to the system wiring while allowing access to
the key panel. A ground strap must be connected between the stud on the inside of the dress panel
and the ground stud in the backbox.
1.7.3 Trim Ring
An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim Ring adds 1.5"
of wall coverage around the backbox, concealing hardware and providing a finished appearance for
a semi-flush mounted panel.
1.7.4 Multi-Module Mounting Bracket
An addressable Multi-Module can be installed inside the FACP backbox using the
MULTIMOD-BRKT module mounting bracket. Refer to the MULTIMOD-BRKT Installation
Document P/N 53547 for additional information.
1.7.5 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery
Charger.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one
100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery
may also be housed in the battery box.
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Product Description