Maintenance Programming Level
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. Pressing
1 or 2 will cause the control panel to enter Walktest Mode and will display the following screen:
From this screen, it is possible to view the walktest log, untested system points or a summary of the
addressable devices tested during the current walktest. The user can select between any of these
screens without interrupting the current walktest session. The walktest session will not end until
the Unit In Walktest screen is exited by pressing the Escape key to return to the Walktest Screen.
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen
similar to one of the following two screens to be displayed:
NO EVENTS IN
WALKTEST LOG
If there are no events in the current walktest session, the first screen will be displayed, indicating no
events have been stored in the walktest log. If any events have been stored, a screen similar to the
second will be displayed indicating the latest event. As walktest events occur, the display will
change to indicate the latest event. All stored events can be scrolled on the screen by pressing the
up or down arrow keys. To return to the first event, press the 1st Event key.
Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the
following screens:
NO POINTS IN
SYSTEM
If the system has no points installed, the first screen will be displayed. If points are installed, the
second screen will be displayed, which allows the viewing of all untested system points and their
status relating to the current walktest session. The up and down arrow keys will allow viewing of
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
Unit In Walktest Screen
ALARM: MONITOR
OR
10*15A 012308 1M006
OR
NORTH CLASSROOM
Z001
UNTESTED POINTS
1D001
SMOKE (PHOTO)
*********************
NOT TESTED
Programming