Installation
2.8.1 Ferrite Clamp Installation
Per FCC requirements, ferrite clamps (supplied) are required on both phone lines. Apply one
clamp per phone line inside the FACP cabinet as shown in Figures 2.11 and 2.13. To install, simply
close the clamp around the phone line until it snaps shut. It is not necessary to loop the phone line
around the clamp.
Simply clasp the clamp
around the phone line.
There is no need to
loop the phone line
around the clamp.

2.9 Optional Module Installation

WARNING: RISK OF ELECTRIC SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
2.9.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connec-
tion to a polarity reversal circuit or a Remote Station receiving unit having compatible rat-
ings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
56
Ferrite Clamp in open position
Figure 2.14 Ferrite Clamp Installation
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Optional Module Installation
Ferrite Clamp in closed position