4Xlmf Led Interface Module (Ms-4 Only) - Fire-Lite MS-2E' MS-4E User Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation
4XLB
4XLMF Module
Front View of RZA-4XF
30

2.6.2.3 4XLMF LED Interface Module (MS-4 only)

The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this
module must follow the requirements as specified in "Power-limited Wiring
Requirements" on page 24.
Important: The 4XLMF module can only be installed on connectors J3 and J5 of the
MS-4 main circuit board.
+24 VDC
1
Out #1
2
Out #2
3
Out #3
4
Out #4
5
System Trouble
6
Sound
7
Resound
8
Connect to corresponding terminals
of RZA-4XF Remote Annunciator
Figure 2.15 4XLMF LED Interface Module
Installation of Optional Modules
Note: Make wiring connections with
system power off. Maximum
wire impedance is 50 ohms per
wiring connection.
Single-gang Box
Side View
MS-2/MS-4 PN 51512:D 10/18/04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-2Ms-4Ms-2eMs-4e

Table of Contents