Programming
NAC #

1=AUTO SILENCE

2=CODING
TEMPORAL
NAC Screen #2
108
Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following
screens will be displayed:
1=30 MINUTES
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the display
will return to NAC Screen #2.
NOTE: All silenceable control modules as well as the remote power supply sync will be
controlled by the Autosilence timer for NAC 1.
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE
Auto Silence Screen #3
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Master Programming Level