Programming
all untested points. If a point is tested while it is being displayed, the screen will update and display
the next untested point. The first line indicates the total number of untested points. The second line
displays information about an untested point. A description on the bottom of the screen will
indicate if the displayed point has been disabled, if the Walktest option has been disabled for that
point or if the point is not yet tested. The up and down arrow keys allow the user to scroll through
all untested points.
Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen
which will show a total of the tested detectors, tested modules, untested detectors and untested
modules for the current walktest session.
To end the Walktest session, press the Escape key to return to the Walktest screen. Pressing 3 for
View Results while viewing the Walktest screen, after a walktest session has been completed, will
allow the operator to view the final results of the most recent walktest.
3.7.5 System
To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2.
The following display will appear:
Pressing 1 while viewing the System Screen will cause the following screen to be displayed:
To change the time, press 1 to display the following screen:
A flashing cursor will appear on the left side of the display. Enter the four digit number
corresponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one
position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will
return to the Time and Date Screen displaying the new time.
154
SYSTEMS
1=TIME/DATE
System Screen
TIME AND DATE
1=TIME
01:00 AM
2=DATE
01-01-2006
Time and Date Screen
ENTER TIME
01:00 AM
1=AM
Time Screen
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Maintenance Programming Level
12HR
2=PM

Advertisement