Programming
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
TIMER
1=AC LOSS DELAY
Timer Screen #2
104
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will
indicate the new delay time.
Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be
programmed for either PAS or Pre-signal operation. Refer to"Edit Detector" on page 67 for
programming details.

Waterflow Delay

A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
RANGE 0-90 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2
to display the following:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss
report immediately to the central station.
WATERFLOW DELAY
Waterflow Delay Screen
AC Loss Delay Screen #1
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010