Read Status
4.22.6 NAC
4.22.7 Relays
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Each NAC can be programmed individually with unique settings with the exception of Canadian
Mode. When the Canadian Option is seletected in programming (see "Canadian Option" on
page 112), all NAC settings are changed to that of NAC 1. While in Canadian Mode, if any NAC is
setting is changed, all other NACs will get those same settings. Pressing 3 while viewing Read
Status Screen #2 will display the following screen:
1=NAC 1
2=NAC 2
The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed
options for NAC 2, 3 to view the programmed options for NAC 3, or 4 to view the programmed
options for NAC 4. The resulting screens will display the following information:
Enable/Disable Status
Circuit Type (Bell, Strobe, etc.)
Silenceable/Nonsilenceable
Auto Silence Enable/Disable and time delay (in minutes)
Coding Selection (Temporal, Steady, etc.)
Zone Assignments
Silence Inhibit Enabled/Disabled
Synchronization Type (System Sensor, Wheelock, or Gentex)
Pressing 1 while viewing Read Status Screen #3 will display the following screen:
1=RELAY 1
2=RELAY 2
3=RELAY 3
The operator can view the programmed option for each relay by pressing the corresponding number
key.
NAC
3=NAC 3
4=NAC 4
RELAY
Operating Instructions
175