Programming

Type

To select the type of detector being programmed, press the 2 key while viewing the Edit Detector
EDIT DETECTOR
1=ENABLED
Screen #2. This will cause the control panel to display the following Detector Type Screens:
2=TYPE

3=VERIFICATION

Edit Detector Screen #2
Pressing the down arrow key will display additional detector types as indicated in the following
table.
While viewing either Detector Type screen, select the type of detector being programmed by
pressing the corresponding keyboard number key. The display will return to Edit Detector Screen
#2 and indicate the selection next to the Type option.
NOTE: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory
point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire
alarm LED or alarm relay, if the detector senses smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2
so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to "Alarm
Verification (None or One Minute)" on page 168.
70
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1
Detector Type
Smoke Photo
User-Defined-1
Smoke Ion
User-Defined-2
Heat Detect
User-Defined-3
Smoke DuctP
User-Defined-4
Photo w/Heat
User-Defined-5
Duct-Superv
User-Defined-6
Photo-SupervAR
User-Defined-7
ADAPT
User-Defined-8
Beam
User-Defined-9
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
same as previous (Smoke Ion)
Fire Alarm
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke DuctP)
Fire Alarm
same as previous (Photo w/Heat)
Supervisory, latching
same as previous (Superv DuctP)
Supervisory, nonlatching (works only in LiteSpeed)
same as previous (Photo-SupervAR)
Fire Alarm
same as previous (ADAPT)
Fire Alarm
same as previous (Beam)
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Master Programming Level