Remote Fire Annunciator; Ann-S/Pg Serial/Parallel Interface Module; Ann-I/O Led Driver Module - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Accessories
A variety of optional annunciation devices can be connected to an ANN-BUS communication
circuit. ANN Series devices can be connected to the primary communication circuit (EIA-
485) terminals on TB9. A secondary communication circuit for these devices is available at
TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators.
Compatible devices include the following:
– ANN-80 LCD Annunciator
– ANN-80C LCD Indicator (Canadian Applications)
– ANN-S/PG Serial/Parallel Printer Interface Module

– ANN-I/O LED Driver Module

– ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
– ANN-RLED Annunciator Module (red alarm LEDs only)
– ANN-RLY Relay Module (can be mounted in the supplied FACP chassis)
– ANN-LC Lite-Connect Module (secondary ANN-BUS only)
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in
the system.
The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS
(TB8) simultaneously.
The panel is capable of operating the ACS-BUS (connector TB9) and the secondary
ANN-BUS (connector TB8) simultaneously.
The secondary ANN-BUS (on connector TB8) does not support legacy ACS annunciators.
The secondary ANN-BUS can be configured to support either terminal mode annunciators,
printer/PC devices, or ANN-BUS devices.
Only one audio system (ECC-50/100 or ACC-25/50) may be connected to the ANN-BUS.
ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It
mimics the display on the control panel and will annunciate device type, point alarm, trouble or
supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP.
The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervi-
sory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely perform-
ing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication
between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employ-
ing the ANN-BUS communication format. The devices are powered, via two additional wires,
from either the host FACP or remote UL-listed, filtered, power supply.
The function buttons, keyswitch and piezo sounder may be individually enabled and disabled
through the FACP software. Refer to "ANN-80 Options" on page 117 for a description of this fea-
ture and programming information.
Note that if the keyswitch is enabled and remains in the unlocked position for more than two min-
utes without any buttons being pressed on the annunciator, a trouble indication will be annunciated.
The ANN-80C (for Canadian applications) does not provide FACP control for Acknowledge,
Reset, Silence, or Drill.

ANN-S/PG Serial/Parallel Interface Module

The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel
printer to the FACP for a real-time log of system events, detector status reports and event history.
The module is provided with a plastic enclosure for surface mounting.
ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The module is provided with a plastic wall mount.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Product Description
23