Wiring Configuration - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Accessories

Wiring Configuration

Figure 1.3 illustrates the wiring between the FACP's Primary ANN-BUS and ANN-BUS devices.
ANN-BUS Device
Figure 1.4 illustrates the wiring between the FACP's Secondary ANN-BUS and ANN-BUS
devices.
B A (+) (-)
TB1
4 3 2 1
ANN-BUS Device
Figure 1.4 Secondary ANN-BUS wiring to ANN-BUS Device
Powering Both ANN-BUS Circuits Simultaneously
When simultaneously using the Primary and Secondary ANN-BUS circuits on the FACP, power
can be shared from the Nonresettable Power output on TB1. Alternately, one ANN-BUS can be
powered by the Resettable Power output (TB1 Terminals 3 and 4) once it is reconfigured as Nonret-
table Power using JP6. This provides the benefit of independently acting power-limiting for the
two ANN-BUS circuits (required for Canadian applications).
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
ANN-BUS and power wiring are
supervised and power-limited
B A (+) (-)
24 VDC
nonresettable
TB1
4 3
2 1
+
TB1
TB2
JP7
+
-
1
REMOTE PWR
NON-RST
2
SUPPLY SYNC
POWER
3
Figure 1.3 Primary ANN-BUS wiring to ANN-BUS Device
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
+
-
TB2
TB1
JP7
+
-
+ 24V -
+ 24V -
1
REMOTE PWR
RST
NON-RST
2
SUPPLY SYNC
POWER
POWER
3
-
TB9
ANN
TB10
ACS
+ 24V -
+ 24V -
A B
RST
+ -
POWER
MS-9200UDLS
Secondary ANN-BUS
TB9
ANN
TB8
ACS
A B
Xmt Rcv Dtr Gnd
A
B
+ -
In+ In- Out+ Out-
MS-9200UDLS
Product Description
Primary ANN-BUS
SLC
SLC
SLC
SHIELD
SLC
B+ A+ B- A-
A
B
TB10
SLC
SLC
SHIELD
SLC
SLC
B+ A+ B- A-
A
B
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents