Zones Available; Zone Message; 4: Loop Setup; Style - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Master Programming Level
ZONE SETUP
1=ZONE TYPES

2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3
3.6.4 Loop Setup
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
Zone Message
Pressing 3 while viewing Zone Setup Screen #3 will display the following screen:
1=Z00
2=Z01
3=Z02
Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number
key corresponding to the Zone to be programmed. Screens will be displayed allowing the
programmer to select Audio Messages 1 through 5. When an audio message is selected, the display
will return to the Zone Message screen, showing the message selected for that particular zone. In
the example above, Zone 01 has been programmed for Audio Message 1.
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6, or 7 wiring and
to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the
following screen to be displayed:

1=STYLE

2=PROTOCOL
Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup
Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as
indicated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle
the display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4
and Style 6. Note that, when programming the Loop Style, the programmer can only select between
ZONES AVAILABLE
ZONE MESSAGE
NO MESSAGE
MESSAGE 1
NO MESSAGE
LOOP SETUP
LITESPEED
Loop Setup Screen
Programming
4
97