Master Programming Level
SERVICE TERMINAL

1=RING COUNT

Service Terminal Screen #2
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Pressing 1 while viewing On Board DACT Screen #2 will cause the following screen to appear:
1=RING COUNT
Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel will
not answer an incoming call. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The following
screen will be displayed:
RANGE 0-25 RANGE
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring count
which can be a value between 00 and 25. After the second digit is entered, the display will return to
the Service Terminal screen.
SERVICE TERMINAL
Service Terminal Screen
RING COUNT
Ring Count Screen
Programming
0
135