Programming
CENTRAL STATION

1=PHONE NUMBER

Primary/Secondary Screen #2
CENTRAL STATION
1=COMM FORMAT
Primary/Secondary Screen #3
140
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour
Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and 2359
= 11:59PM).
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be
displayed:
20 NUMBERS MAXIMUM
The Phone Number screen is used to enter the Central Station phone number that the DACT will be
contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - C
where A = *, B = # and C = 2 seconds pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press
the right arrow key to move the cursor to the right one position. Enter the second digit and repeat
the process until all digits are entered. Press the Enter key to store the phone number in memory.
Enter the digits as you would like the number to be dialed. For example, if it's necessary to dial 9
before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9
followed by D for a three second pause or E for a five second pause then the phone number
followed by an F to indicate the end of the number.

Communication Format

Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
1=ADEMCO CONTACT ID
2=SIA 8
3=SIA 20
The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any
format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Screen Selection
ADEMCO CONTACT ID
SIA 8
SIA 20
PHONE NUMBER
Phone Number Screen
COMM FORMAT
Communication Format Description
Contact ID, DTMF, 1400/2300 ACK
Security Industry Association, 8 messages per call
Security Industry Association, 20 messages per call
Table 3.10 Communication Formats