Fire-Lite MS-9200UDLS Manual page 34

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Product Description
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 1.9. After the ANN-
I/O is connected to the panel, it must be added to the system via FACP programming. Refer to the
section titled "ANN-I/O Options" on page 122.
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so
that there is approximately 10 mA of current for each LED. No series resistors are required. LED
outputs can be mapped to output circuits. Refer to the programming section titled "ANN-I/O
Options" on page 122 of this manual.
The LEDs are wired as illustrated in Figure 1.10. Note that the illustration depicts only connectors
P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
34
P1
11
1
10
ANN-I/O Module
24 VDC
nonresettable
+
-
TB2
TB1
JP7
+
-
1
+ 24V -
+ 24V -
REMOTE PWR
NON-RST
RST
2
SUPPLY SYNC
POWER
POWER
3
Figure 1.9 ANN-I/O Connection to FACP
P2
P3
21
30
20
31
ANN-BUS and power wiring are
supervised and power-limited
TB9
ANN
TB10
SLC
B+ A+ B- A-
ACS
A B
+ -
MS-9200UDLS
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Accessories
P4
40
Primary ANN-BUS
SLC
SLC
SLC
SHIELD
A
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents