Product Description
FACP Input programmed to Zone 33 goes into alarm, the programmed message for Zone 33
[Message 1, 2, 3, 4 or 5] will play over the ACC-25/50ZS Series output circuit 1 which
corresponds to FACP Zone 33.
FACP Input programmed to Zone 1 and Zone 34 (Zone 1 is programmed for a Message [1, 2,
3, 4 or 5] and Zone 34 is programmed for No Message) goes into alarm, the programmed
message for Zone 1 will play over the ACC-25/50ZS Series output circuit 2 which corresponds
to FACP Zone 34.
If two or more input zones are active at the same time, the highest priority message will turn on
(Message 1 is highest priority and Message 5 is lowest) and play over the corresponding audio
panel output circuit(s).
Zone 32 is an All-Call zone. All audio panel output circuits will turn on if Zone 32 is activated
and its programmed message will play (or the highest priority message currently being
played).
A fault at the ACC-25/50ZS Series panel will cause the FACP to indicate a System Trouble and the
display will indicate a Voice Evac Fault.
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of commu-
nication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals
2 & 3 of the ACC-ZPMK module on the audio panel.
Figure 1.16 FACP Connection to ACC-25/50ZS(T) Series Audio Panel
40
+ -
ACC-ZPMK
on ACC-25/50ZS(T) Series
A (+)
TB5
TB6
TB8
NO NC C
NC NO C
Xmt Rcv Dtr Gnd
A
B
In+ In- Out+ Out-
MS-9200UDLS
S1
ON
TENS ONES
O N
1 2 3 4 5 6 7 8
S3
S2
B (-)
Primary ANN-BUS
TB9
TB10
+
-
B+ A+ B- A- A B
A
B
Slc Slc Slc Slc Shield
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Accessories