Erase History; 8: Walktest - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming
3.6.8 Walktest
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
114

Erase History

The Erase History option allows a user to erase all events from the history file. This will provide a
clean slate in order to use the history file to track future events. Pressing 2 while viewing the
History Screen will display the following screen:
1=YES
Pressing 1 while viewing the Erase History Screen will erase all events from the History file.
During this process, the display will read as follows:
After the History file has been erased, the display will return to the History Screen.
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Pressing 2 while viewing the Programming Screen #3 will cause
the following Walktest options to be displayed:
1=SILENT
2=AUDIBLE
3=VIEW RESULT
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed::
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
ERASE HISTORY
PROCEED ?
2=NO
Erase History Screen
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
WALKTEST
Walktest Screen
UNIT IN WALKTEST
Unit In Walktest Screen
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010