2.7 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. A typical wiring diagram for the MS-9200UDLS is shown
below.
AC Power
Grounding
Stud (see
Figure 2.5)
Wire Nut
Figure 2.11 Typical UL Power-limited Wiring Requirements
54
Power-limited Circuits (Class 2)
Nonpower-limited Circuits
To Batteries
Ground Cable #71073
UL Power-limited Wiring Requirements
Power-limited Circuits (Class 2)
Nonpower-limited Circuits
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Power-limited
Circuits (Class 2)
maintain minimum
0.25" between
power-limited and
nonpower-limited
circuits wiring
Ferrite Clamps
(See Section 2.8.1
for for more
information.)
Nonpower-limited
Circuits