Master Programming Level
OPTION MODULES
1=ANNUNCIATORS
2=ON BOARD DACT
3=PRINTER/PC
Option Module Screen
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the
Silence button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil
Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never
functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the
Reset button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst
Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never
functions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the
Drill button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl
Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never
functions).

Onboard DACT

The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a
central station. Pressing 2 while viewing the Option Module Screen will cause the following
screens to be displayed:
1=ENABLED
2=PRIMARY PHONE
3=SECONDARY PHONE
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
Onboard DACT Enable
To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1 until the display
reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press
of the key.
Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary phone line being
connected to the DACT. The following screen will be displayed:
1=TYPE
ON BOARD DACT
On Board DACT Screen #1
ON BOARD DACT
On Board DACT Screen #2
ON BOARD DACT
PRIMARY PHONE LINE
TOUCHTONE
Primary Phone Line Screen
Programming
YES
133