Fire-Lite MS-9200(C) Instruction Manual

Fire-Lite MS-9200(C) Instruction Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200(C):
Table of Contents

Advertisement

PN: 51003:E
ECN 02-014
Addressable Fire Alarm
Control Panel
MS-9200(C)/MS-9200E
Document
#51003
E
01/11/02
Rev.
© 2002 Fire•Lite

Advertisement

Table of Contents
loading

Summary of Contents for Fire-Lite MS-9200(C)

  • Page 1 PN: 51003:E ECN 02-014 Addressable Fire Alarm Control Panel MS-9200(C)/MS-9200E Document #51003 01/11/02 Rev. © 2002 Fire•Lite...
  • Page 2 While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede- ing devices, and a fire alarm control with remote notification termined rate or reaches a predetermined level.
  • Page 3 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to light- of power before servicing.
  • Page 4 Notes Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 5: Table Of Contents

    Table of Contents CHAPTER 1: Product Description ......................... 9 1.1: Features ...............................9 1.2: Specifications ..............................11 1.3: Controls and Indicators ..........................12 1.4: Circuits ................................13 1.5: Components..............................13 1.5.1: Intelligent Addressable Detectors: Newer Series................14 1.5.2: Intelligent Addressable Modules: Newer Series ................15 1.5.3: 300 Series Intelligent Addressable Devices..................15 1.5.4: Addressable Device Accessories.......................16 1.6: Optional Modules ............................16 1.7: Accessories..............................17...
  • Page 6 Table of Contents 3.4.4: Set Time and Date ..........................50 3.4.5: Check..............................50 CHAPTER 4: Operating Instructions ........................51 4.1: Control Switches (Keys)..........................51 4.1.1: Acknowledge/Step ..........................51 4.1.2: Alarm Silence ............................51 4.1.3: Drill Hold 2 Sec..........................51 4.1.4: System Reset .............................51 4.2: LED Indicators ............................52 4.3: Normal Operation............................52 4.4: Trouble Operation............................53 4.5: Alarm Operation............................55...
  • Page 7 This control panel has been designed to comply with standards set forth by the following regulatory agencies: • Underwriters Laboratories Standard UL 864 • NFPA 72 National Fire Alarm Code • CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents.
  • Page 8 MS-9200(C) Main Circuit Board TB7 - TERM COMM TB1 - Bell Circuit 1 TB3 - Relays PC/Printer B (-) TROUBLE OUT (+) A (-) IN (+) A (+) OUT (-) B (+) IN (-) TB2 - Bell Circuit 2 ALARM TB5 - ACS COMM B (-) 1 (+)
  • Page 9: Chapter 1: Product Description

    Product Description Product Description CHAPTER 1 The Fire•Lite MS-9200(C) is a compact, cost effective, addressable FACP (Fire Alarm Control Panel) with an exten- sive list of powerful features. The combination of Fire•Lite's newer series devices and legacy 300 Series Addressable Devices, along with the MS-9200 FACP offers the latest in fire protection technology.
  • Page 10 Features • Remote ACK/Silence/Reset/Drill via MMF-300, MMMF-301 modules, AFM annunciators or LCD-40 Remote Fire Annunciator • Auto-program (learn mode) reduces installation time • Password and key-protected nonvolatile memory • User programmable password • Fully programmable from panel keyboard • Programmable from an off-line PC •...
  • Page 11: Specifications

    Specifications Specifications AC Power - TB8 MS-9200(C): 120 VAC, 50/60 Hz, 2.3 amps MS-9200E: 240 VAC, 50 Hz, 1.2 amps Wire size: minimum #14 AWG (2.00 mm ) with 600V insulation Battery (Lead Acid Only) - J3 Maximum Charging Circuit: Normal Flat Charge —...
  • Page 12: Controls And Indicators

    Controls and Indicators Nonregulated Special Purpose 24 VDC Power - TB4, Terminals 1(+) & 2(-) Operating voltage range: 18V to 30V Total DC current available for powering external devices is 2.5 amps This power is not to be used for ACS, LDM or LCD-40 annunciators Power-limited circuit Controls and Indicators LCD Display...
  • Page 13: Circuits

    Circuits Circuits SLC Communication Loop One SLC loop, configurable for NFPA Style 4, 6 or 7, is provided for communication to addressable monitor (initiat- ing device) and control (output device) modules. Refer to SLC Wiring Manual for additional information. Output Circuits The following output circuits are available on the FACP: •...
  • Page 14: 1: Intelligent Addressable Detectors: Newer Series

    Components Transformer Assembly Standard One 100VA transformer is provided standard with the panel (3.6 amps maximum). An optional 100 VA transformer XRM-24 (XRM-24E for the MS-9200E) is available to provide maximum accessory power (6.6 amp total). Optional XRM-24 Batteries Battery Cable P/N 75287 The MS-9200 cabinet provides space for two batteries up to 12 Amp Hour.
  • Page 15: 2: Intelligent Addressable Modules: Newer Series

    Components 1.5.2 Intelligent Addressable Modules: Newer Series The newer series of Control Modules and Monitor Modules provide an interface between the control panel and con- ventional notification and initiating devices. Each module can be set to respond to a maximum address of 99 with built-in rotary switches.
  • Page 16: 4: Addressable Device Accessories

    Optional Modules 1.5.4 Addressable Device Accessories E.O.L. Resistor Assemblies The 47K End-of-Line Resistor Assembly is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9K End-of-Line Resistor Assembly is used to supervise the MMF-302 module circuit. The resistors are included with each M300 and C304 module.
  • Page 17: Accessories

    Accessories PK-9200W Kit for Local Downloading The PK-9200W Programming Utility can be used to program an MS-9200 directly from most IBM PC/XT/AT or compatible computers, including laptops and portables, equipped with a serial port. MS-9200 program files can also be created and stored on the PC, then downloaded to the control panel. The PK-9200W Kit includes the MS-9200 Windows based Programming Utility software on four 3½"...
  • Page 18: 2: Battery Box

    Accessories 1.7.2 Battery Box BB-17F The BB-17F battery box may be used to house two 12 AH or 18 AH batteries. The battery box mounts directly below the MS-9200 cabinet. The box is red and is provided with knockouts. BB-55F The BB-55F battery box may be used to house two 25 AH batteries, two 55 AH batteries or one 100 AH battery.
  • Page 19 Accessories Wire the CHG-120F to the MS-9200 as shown. Cut Jumper JP1, which is only on the newer versions of the MS-9200 main circuit board, to disable the FACP battery charger when using the CHG-120F. Wire the batteries to the CHG-120F but do not connect the Battery Interconnect cable until the system is ready for testing.
  • Page 20: 4: Annunciators

    Accessories 1.7.4 Annunciators LED Zone Type Annunciators The ACS Series Annunciators remotely display system status. The ACM/AEM-16ATF annunciators display zone alarm and trouble status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The ACM/AEM-32AF annunciators display zone alarm status only and provide no remote system switch functions. For more detailed information, refer to the appropriate ACS Annunciator manual.
  • Page 21 Accessories LCD-40 Series Remote Fire Annunciators The LCD-40 Series, consisting of the LCD-40 and LCD-40L, are com- FIRE ALARM ANNUNCIATOR pact, attractive, 40-character backlit LCD fire annunciators that are capable of displaying English-language text. They mimic the display on the MS-9200 main control circuit board and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment Drill ®...
  • Page 22: 5: Fcps-24F/E Remote Field Charger Power Supply For System Power Expansion

    Accessories 1.7.5 FCPS-24F/E Remote Field Charger Power Supply for System Power Expansion The FCPS-24F/E is a compact, remote power supply with battery charger. This remote power supply consists of a fil- tered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits [four Style Y (Class B) or two Style Z (Class A) and two Style Y (Class B)].
  • Page 23: Chapter 2: Installation

    Installation Installation CHAPTER 2 Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left.
  • Page 24: Backbox Mounting

    Backbox Mounting Backbox Mounting Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Two stand- offs support the board in the center. Set the board aside in a safe, clean place. Avoid static discharge which may damage the board.
  • Page 25: Power

    Power Power WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized. 2.2.1 AC Power and Earth Ground Connections Primary power required for this panel is 120 VAC, 50/60 Hz, 2.3 amperes for the MS-9200(C) or 240 VAC, 50/60 Hz, 1.2 amperes for the MS-9200E.
  • Page 26: Standard Relays

    Standard Relays Standard Relays The MS-9200 provides a set of Form-C alarm and Form-C trouble contacts rated for 2.0 amps @ 30 VDC (resistive). The panel also provides a Form-A supervisory contact rated for 2.0 amps @ 30 VDC (resistive). Refer to Figure 2-7 on page 27 for UL power-limited wiring requirements.
  • Page 27: Ul Power-Limited Wiring Requirements

    UL Power-limited Wiring Requirements UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
  • Page 28: Wiring The Signaling Line Circuit

    Wiring the Signaling Line Circuit Wiring the Signaling Line Circuit The MS-9200 communicates with addressable initiating, monitor and control devices through a Signaling Line Cir- cuit (SLC) loop, which can be wired to meet NFPA requirements for Style 4, Style 6 or Style 7. 2.7.1 Device Capacity The capacity of the MS-9200 includes up to 99 addressable detectors and an additional combination of up to 99 addressable pull stations, control modules and monitor modules.
  • Page 29: Optional Modules

    Optional Modules Optional Modules The MS-9200 supports option modules using connectors J6, and J16 on the main circuit board. There are two optional modules available for the MS-9200: • RTM-8F Relay/transmitter Module • UDACT-F Universal Digital Alarm Communicator/Transmitter Note that older versions of the MS-9200 main circuit board do not have connector TB7 which allows connection of a PC, printer or Terminal Mode annunciator.
  • Page 30 Optional Modules WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring UDACT-F Mounting Options ABS-8RF FIGURE 2-10: The UDACT-F may be mounted directly to the MS-9200 main circuit board or remotely in an ABS-8RF or UBS-1F enclosure up to 6,000 feet (1,800 m) away from the control panel.
  • Page 31 Optional Modules External UDACT-F Mounting in ABS-8RF FIGURE 2-12: Supervised and Power-limited ACS (EIA-485) and power connections. Surge protection can be provided by using one of the UL listed compatible surge suppressors listed in the Fire•Lite Device Compatibility Document. +24 VDC Nonresettable Solid Earth Power (TB4)
  • Page 32: 2: Acm-8Rf Relay Control Module

    Optional Modules 2.8.2 ACM-8RF Relay Control Module ABS-8RF Enclosure FIGURE 2-13: WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. When installed with an MS-9200 FACP, the ACM-8RF mod- ules provide relay activation for each of the 56 possible FACP zones plus special functions.
  • Page 33: 3: Rtm-8F Option Module Installation

    Optional Modules 2.8.3 RTM-8F Option Module Installation WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring Insert the three supplied nylon standoffs into the holes located on the right-side edge of the MS-9200 main circuit board.
  • Page 34 Optional Modules RTM-8F Relay Transmitter Module Components RTM-8F Relay Transmitter Module FIGURE 2-16: Local Energy Municipal Box Trouble LED (yellow) JP1 - Cut for Polarity Reversal Remote Station operation Zone 1 JP2 - Jumper Settings: Zone 2 Alarm/Trouble Polarity Reversal Remote Station (Power-limited) Zone 3 Note: If relays are used as...
  • Page 35: Printer/Pc And Terminal Mode Annunciator Interface

    Printer/PC and Terminal Mode Annunciator Interface Printer/PC and Terminal Mode Annunciator Interface A serial printer, personal computer or Terminal Mode annunciator may be connected to TB7 on the FACP main cir- cuit board. Switch SW3, located on the bottom center of the main circuit board, must be set to configure terminal block TB7 for the appropriate device.
  • Page 36 Printer/PC and Terminal Mode Annunciator Interface PIM-24 Interface Module Older versions of the MS-9200 main circuit board do not have a TB7 connector for direct connection of a PC or printer. These older boards require the Printer/PC Interface Module P/N PIM-24 to provide an EIA-232 conversion for adaptation to most 40 and 80 column printers and most IBM PC/XT/AT or compatible computers including lap- tops and personal computers.
  • Page 37: Chapter 3: Programming/Read Status

    Programming/Read Status Programming/Read Status CHAPTER 3 NOTE: This chapter provides a detailed description of the FACP programming. For your convenience, a Program- ming Flowchart has been included in “Screen Options Flowchart” on page 84. It may be helpful to follow along with the flowchart as this chapter is reviewed.
  • Page 38: Initial Power-Up

    Initial Power-up 1 = Programming: There are two programming levels. • Program Level 1 is for system configuration in which data relating to device types, zoning, messages, etc. is entered into the system memory • Program Level 2 is where a qualified operator can access features such as Disable, Clear History, Walktest, Time Change and Program Check.
  • Page 39: Programming

    Programming Programming Press the ENTER key. The screen below will appear: 1 = PROGRAMMING 2=RD STATUS 3=RD BAT To enter the programming mode, press '1'. The display will read as follows: KEY PASSWORD, ENTER Entering the Level 1 password (default 00000) will cause the following screen to appear (refer to “Program Change - Level One”...
  • Page 40: Program Change - Level One

    Program Change - Level One Program Change - Level One When the correct password is entered, the MS-9200 will enter Level 1 program mode. In this mode, the trouble relay is activated and the System Trouble LED flashes and cannot be changed to steady and the piezo sounder is off. The following display will appear: 0=CLR 1=AUTO 2=POINT 3=SYS 4=PWORD 5=LOAD...
  • Page 41 Program Change - Level One New Detectors For each new detector, the Autoprogram feature selects default program values and presents the information to the user. A typical example follows: PROGRAM SMOKE DET P01 <ADJ> <NOUN> In the preceding example: • 'P' in 'P01' represents the actual type code (photoelectric) of the detector found at address 01. ('I' would repre- sent an Ionization detector) •...
  • Page 42 Program Change - Level One Altering the NOUN field is done in a similar way. Use the up or down arrow keys to step through the NOUN library which is listed below: HVAC_ROOM _________ (default of blanks) KITCHEN__ BASEMENT_ LOBBY____ BOILER_RM OFFICE___ CLASSROOM...
  • Page 43 Program Change - Level One If ENTER is pressed, the device is deleted from memory and autoprogram displays the next new device. If the left arrow is pressed, the program is unchanged and the next new device is displayed. After all new detectors are presented for editing, the autoprogram feature displays the modules on the SLC loop start- ing with the device found at the lowest address.
  • Page 44: 3: Point Edit

    Program Change - Level One Control modules default to Zone 00 (general alarm). All type code options are silenceable except Relay and Strobes. The selection of control module type codes may change their function. Select the type code from the library list below.
  • Page 45: 4: System Edit

    Program Change - Level One 3.3.4 System Edit The System Edit function is selected by pressing '3'. The system edit screen appears as shown below for software releases prior to P/N 73750. This software does not support the LCD-40 Annunciator. VF=N SI=N AS=N PS=N CD=N AN=N ST=4 REM=N Use the up and down arrow keys to scroll through the choices for each option and the left and right arrow keys to...
  • Page 46: 5: Password Change

    Program Change - Level One There are nine system function options for software P/N #M9200V20 or greater. The factory default selections and user option selections are shown below: FUNCTION DEFAULT SELECTION V = Alarm Verification (N)one (Y) 73 seconds I = Silence Inhibit (N)one (Y) 60 seconds A = Autosilence...
  • Page 47: 6: Load

    Program Change - Level 2 3.3.6 Load While displaying the Program Menu, program selection '5' sets up the MS-9200 for transfer of its application data- base from/to a DOS-based or Window-based computer. This may be used to save the program that exists in an MS-9200 for security and future service reasons;...
  • Page 48: 1: Disable

    Program Change - Level 2 Enter the Level 2 password (default = 11111) then press the ENTER key to access Programming Change Level 2. The screen shown below will appear: 1=DISABL 2=CLR HIST 3=WALK 4=TIME 5=CHEK From this screen, the available function choices include point Disable, Clear History, Walktest, Set Time and Check programming.
  • Page 49: 2: Clear History

    Program Change - Level 2 3.4.2 Clear History Pressing '2' displays the following screen: ENTER TO CLEAR HIST. BACKSPACE TO ESCAPE Press the ENTER key to clear the 500-event History file. Press the left arrow key (backspace) to exit without clearing the History file.
  • Page 50: 4: Set Time And Date

    Program Change - Level 2 Note that if the system under test includes one or more enabled MMF-302 monitor modules, the following may apply: If the MMF-302 monitor module is used for a supervised, 2-wire smoke zone, alarming any monitor module in the system will result in the activation of programmed control outputs for an additional eight seconds or less.
  • Page 51: Chapter 4: Operating Instructions

    Operating Instructions Operating Instructions CHAPTER 4 FIRE SUPER- ALARM SYSTEM POWER ALARM VISORY SILENCE TROUBLE SYSTEMS ALL NORMAL 10:12 A MON 01/03/00 ACKNOWLEDGE ALARM DRILL SYSTEM STEP SILENCE HOLD 2 SEC RESET ENTER RECALL Control Switches (Keys) 4.1.1 Acknowledge/Step The Acknowledge/Step key silences the piezo sounder and changes all flashing LEDs to steady. Only one press is necessary regardless of the number of new alarms, troubles or supervisory signals.
  • Page 52: Led Indicators

    LED Indicators LED Indicators The six LED indicators on the front panel operate as follows: AC Power This is a green LED which illuminates if 120 VAC power is applied to the MS-9200(C) or 240 VAC power is applied to the MS-9200E. Fire Alarm This is a red LED that flashes when one or more alarms occur.
  • Page 53: Trouble Operation

    Trouble Operation Trouble Operation With no alarms, the detection of a trouble in the system will cause the piezo to sound, the System Trouble LED to flash and the trouble relay to activate. A message will appear on the LCD display indicating the trouble condition. The same message is sent to the printer and history file along with time and date.
  • Page 54 Trouble Operation Monitor and Control Modules The following is a typical message that could appear on the LCD display for monitor modules and control modules in trouble. TRBL # MONITOR M01 <ADJ> <NOUN> The information displayed in the first line in the previous example provides the following information: •...
  • Page 55: Alarm Operation

    Alarm Operation If multiple trouble conditions exist in the system, they will be scrolled on the LCD display automatically at a three second rate. If a combination of alarms, troubles and/or supervisory conditions occur in the system simultaneously, only the alarms are scrolled on the display. If the Acknowledge/Step key is pressed, the display stops on the present item for one minute or until the Acknowledge/Step key is pressed again.
  • Page 56: Nac (Notification Appliance Circuit) Operation

    NAC (Notification Appliance Circuit) Operation NAC (Notification Appliance Circuit) Operation There are two NACs on the MS-9200. For software releases prior to P/N 73750, NAC 1 is programmable and factory defaulted to general alarm, silenceable and March Time coding operation. NAC 2 is not programmable and is fixed as general alarm, nonsilenceable and may not perform coded functions.
  • Page 57: 4.10 Time Functions: Real-Time Clock

    Time Functions: Real-Time Clock 4.10 Time Functions: Real-Time Clock The MS-9200 includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 hour time with month/day/year and is stored in RAM. If both AC and battery power are lost, the time must be reset. 4.11 Coded Operation - NAC 1 and NAC 2 Shown below are the pulse rate outputs via NAC 1 or NAC 2 when coded operation is selected.
  • Page 58: 4: Alarm Verification

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
  • Page 59: Read Status

    Read Status The operator presses '2' and the Read Status display shows: DISPLAY POINT=*/#,AA HISTORY=1 PRINT=2 From the display shown above, an operator may select one of the choices as listed below: • To Display Point Status, the type of device to be read must first be identified by pressing the * key for a detec- tor or the # key for a module.
  • Page 60 Read Status Read History The MS-9200 has a 500-event history buffer. Stored events include Point Status, System Troubles, and Acknowl- edge/Step, Alarm Silence, Drill and System Reset key presses. All events are recorded with the time and date. His- tory events are stored in volatile memory, therefore, removal of primary AC power and secondary battery power will clear the history buffer.
  • Page 61: Appendix A: Power Supply Calculations

    Power Supply Calculations Power Supply Calculations Appendix A A.1 The AC Branch Circuit The MS-9200 requires connection to a separate dedicated 120 VAC branch circuit, which must be labeled Fire Alarm. The branch circuit must connect to the line side of the main power feed of the protected premises. No other equip- ment may be powered from the fire alarm branch circuit.
  • Page 62: A.2: The Main Power Supply

    Power Supply Calculations A.2 The Main Power Supply The MS-9200 provides filtered power for operating the fire alarm control panel, operating external devices and oper- ating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the MS-9200 power supply.
  • Page 63 Power Supply Calculations Filtered Load in Alarm - External Devices Connected to TB2 & TB4 Only TABLE A-3: Alarm Current Total Current Device Type # of Devices (amps) (amps) Main Circuit Board 0.168 0.168 RTM-8F ] one max. 0.146 ACM-8RF 0.158 ACM-16ATF ] one max.
  • Page 64 Power Supply Calculations Battery Calculations TABLE A-4: Standby Load Required Standby Time in Hours Current (amps) (24 or 60 Hours) __________ Alarm Load Required Alarm Time in Hours Current (amps) (i.e. 5 minutes = 0.084) __________ Add Standby and Alarm Load for Required Ampere Hour Battery __________ Multiply by the Derating Factor or 1.2 X 1.2...
  • Page 65: Appendix B: Software Zones

    Software Zones Software Zones Appendix B Setup and configuration of an addressable system is quite different than a conventional system. In a conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors, etc.) to zones is straight forward. Wiring is direct from clearly marked panel terminals to any device assigned to a particular zone.
  • Page 66 Software Zones Correlation of Inputs and Outputs to Zones Zoning Example FIGURE B-1: Input Devices Zones Output Devices SD350 SD350 ZONE CMF-300 MMF-300 CMF-300 MMF-301 CMF-300 CP350 ZONE CMF-300 CP350 CMF-300 SD350 SD350 ZONE CMF-300 CP350 CMF-300 Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 67 Software Zones Detector Programming Sheet Example TABLE B-1: DETECTOR ZONE ASSIGNMENT Device Zone Device Zone ADJ (5 charact. max) ADJ (5 charact. max) Address Type Number Address Type Number NOUN (9 charact. max) NOUN (9 charact. max) SD350 FIRST HALL SD350 ELEV.
  • Page 68 Software Zones Module Programming Sheet Example TABLE B-2: MONITOR/CONTROL MODULE ZONE ASSIGNMENT Device Zone Device Zone ADJ (5 charact. max) ADJ (5 charact. max) Address Type Number Address Type Number NOUN (9 charact. max) NOUN (9 charact. max) MMF-300 WEST HALL MMF-301 EAST STAIRWELL CMF-300...
  • Page 69 Software Zones Blank Zoning Sheet FIGURE B-2: Input Devices Zones Output Devices Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 70 Software Zones Blank Detector Programming Sheet TABLE B-3: DETECTOR ZONE ASSIGNMENT Device Zone Device Zone ADJ (5 charact. max) ADJ (5 charact. max) Address Type Number Address Type Number NOUN (9 charact. max) NOUN (9 charact. max) Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 71 Software Zones Blank Module Programming Sheet TABLE B-4: MONITOR/CONTROL MODULE ZONE ASSIGNMENT Device Zone Device Zone ADJ (5 charact. max) ADJ (5 charact. max) Address Type Number Address Type Number NOUN (9 charact. max) NOUN (9 charact. max) Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 72: Appendix C: Lcd-40 Series Annunciator Wiring

    LCD-40 Series Annunciator Wiring LCD-40 Series Annunciator Wiring Appendix C The following drawing illustrates the wiring of two LCD-40 Series Remote Annunciators to an MS-9200 FACP. A maximum of 32 LCD-40 Series annunciators may be connected to a single control panel. The EIA-485 wiring must pass through a ferrite core (P/N FBD-1) in each LCD-40 Series.
  • Page 73: Appendix D: Acs And Ldm Series Wiring

    ACS and LDM Series Wiring ACS and LDM Series Wiring Appendix D The following illustrations show the various configurations which may be wired utilizing ACS Series Annunciators. LDM Series Annunciators may be used in a similar manner. All illustrations show power supplied to annunciators by the MS-9200.
  • Page 74 ACS and LDM Series Wiring The following configuration provides 56 zones of alarm indication, a System Trouble LED, an On Line/Power LED, local piezo sounder and a local Silence/Acknowledge switch. ACM-32AF AEM-32AF Ribbon 24V UNREG 24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV ALARM...
  • Page 75 ACS and LDM Series Wiring The following configuration provides 16 red alarm LEDs, System Trouble LED, On Line/Power LED, local Silence/ Acknowledge switch and piezo sounder. All AFM-16AF annunciators will show the same information. EIA-485 Power MS-9200 24V UNREG 24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV...
  • Page 76 ACS and LDM Series Wiring The following configuration allows the annunciation of 56 zones on the first two annunciators. 56 zones are annunci- ated on the second four annunciators. The same 56 zones are annunciated on the last four annunciators (which dupli- cate the previous set).
  • Page 77: Appendix E: Nfpa Standard-Specific Requirements

    NFPA Standard-Specific Requirements NFPA Standard-Specific Requirements Appendix E The Fire•Lite MS-9200 has been designed for use in commercial, industrial and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appen- dix.
  • Page 78 NFPA Standard-Specific Requirements NFPA Signaling Systems for Central Station Service (Protected Premises Unit) The following figure illustrates an example of Central Station/Remote Station Reporting using an MS-5012. The relay contacts from the MS-9200 may be used to trip any dialer UL listed for Central Station/Remote Station Services.
  • Page 79 NFPA Standard-Specific Requirements The following figure illustrates an example of Central Station/Remote Station Reporting using a 411UD. The relay contacts from the MS-9200 may be used to trip any dialer UL listed for Central Station/Remote Station Reporting Services. Fire•Lite MS-9200 Connection to 411-UD FIGURE E-2: Note:The MMF-300 monitor module input, which is being used to monitor the 411-UD...
  • Page 80 NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System All connections are power-limited and supervised. This applications is not suitable for separate transmission of sprinkler supervisory or trouble conditions. Notes: 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. Cut JP4 on the MS-9200 main circuit board to supervise placement of RTM-8F module and circuit.
  • Page 81 NFPA Standard-Specific Requirements NFPA 72 Remote Station Protective Signaling System Notes: Cut Jumper JP4 on the MS-9200 main circuit board to supervise placement of the RTM-8F module. Refer to Figure 2-7, “Typical UL Power-limited Wiring Requirements,” on page 27, and “UL Power-limited Wiring Requirements”...
  • Page 82 NFPA Standard-Specific Requirements NFPA 72 Proprietary Protective Signaling Systems Proprietary Protective Signaling System FIGURE E-5: MS-9200 Addressable Fire Control Panel MS-9200 Main Board Form-C Alarm contact programmed to activate on General Alarm. Form-C Trouble contact which will automatically activate on any Trouble condition.
  • Page 83: Appendix F: Wire Requirements

    Wire Requirements Wire Requirements Appendix F T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m). Connecting external system accessories to the MS-9200 main circuits must be carefully considered to ensure proper operation.
  • Page 84: Appendix G: Screen Options Flowchart

    Screen Options Flowchart Screen Options Flowchart Appendix G (Software P/N 73750 or greater) Trouble in System No Device Installed SYSTEM TRBL_#<type><addr> NORMAL <adj><noun> Z## (SYSTEM (UNPROGRAMMED SYSTEM) TROUBLE) Trouble in System Press Program Corrupted 'ENTER' 1=Programming 2=Read Status 3=Read Battery Write Protect Press '1'...
  • Page 85 Screen Options Flowchart Press '2' Display Point = */#, AA History = 1 Print = 2 Press ** Press *#AA Press **AA Press *AA Press #AA Press '1' Press '2' Press 'ENTER' Press 'ENTER' Press 'ENTER' Press 'ENTER' Press 'ENTER' EXAMPLE: EXAMPLE: EVENT HISTORY START...
  • Page 86 Notes Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 87 Numerics 300 Series D350P 14 see Addressable Devices Data smoke detector 56, 59 detector data 60 acceptable range 60 ABS-8RF 31, 32 detector sensitivity AC Power 11 acceptable range 60 ACM-8RF 16 Detectors 14 see also Relay Control Module DIM-485 17, 72 Addressable Devices 9, 10, 14 Disable 48 Accessories 16...
  • Page 88 Temporal Code 57 see also Communication Loop Style 6 58 see also Notification Appliance Circuits 26 smoke detector NFPA Standard 77 chamber reading 60 Normal 52 data 56, 59 Notification Appliance Circuits 11, 13, 26, 56 data, printout 60 Specification 11 printout 60 Style Y 26 sensitivity 60...
  • Page 89 Notes Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 90 Notes Document #51003 Rev.E 01/11/02 P/N 51003:E...
  • Page 91 Limited Warranty The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service.
  • Page 92 World Headquarters One Fire-Lite Place, Northford, CT 06472-1653 USA 203-484-7161 • Fax 203-484-7118 www.firelite.com...

This manual is also suitable for:

Ms-9200e

Table of Contents