Programming
EDIT CONTROL
1=ENABLED
2=TYPE

3=SILENCEABLE

Edit Control Screen #2
EDIT CONTROL

1=WALKTEST

2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
88
While viewing one of the Control Type screens, select the type of control module being
programmed by pressing the corresponding keypad number key. The display will return to the Edit
Control Screen #2 and indicate the new type selection.
NOTE: A control relay module set to the Resettable Power type will follow the main circuit board
24 VDC resettable power unless the control relay module is disabled.
The following table contains control module type codes and their functions which are displayed in
the Control Type screens:
Control Type
Bell Circuit
Horn Circuit
Sounders
Relay
Strobe Circuit
Control
Resettable Power
HVAC SHUTDN
1 When using a control relay module to supply resettable
power to conventional 2-wire smoke detectors, the
addressable monitor module must be programmed for
Smoke-Conventional operation
2 For HVAC SHUTDN description, refer to "Control
Module Operation" on page 211.
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the
control module can be silenced, either by pressing the Alarm Silence key or by enabling
Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable
feature causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the
display to toggle between Silenceable Yes and Silenceable No.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to "Walktest" on page 169 for additional information.
Special Function
NAC Type - supervised
NAC Type - supervised
NAC Type - supervised
Ignore Open Circuit
NAC Type - supervised
NAC Type - supervised
1
Relay Type - Ignore Open Circuit
2
Relay Type - Ignore Open Circuit
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010