Operating Instructions
Each ANN-LED can support up to 10 zones.
Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.

4.8 Hazard/Tornado Condition Operation

Hazard/Tornado operation is intended for Manual activation.
Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses ¼ second On, ¼ second Off
The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones, and time/date
Communicate the hazard condition to the Central Station (if the default event code has been
changed from 000 to a reportable event code)
Relays programmed for hazard will be activated
The alarm relay is not activated
Fire Alarm NACs will not activate
SLC NACs (control modules) will activate
Timers are not started
Store event in history buffer
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Each ANN-LED can support up to 10 zones.
Hazard conditions latch. They can be assigned to software zones.

4.9 Medical Alert Condition Operation

Medical alert operation is:
not intended for nurse call stations (applications) per UL1069.
not intended for signaling professional medical staff.
to be used for summoning security guards or other trained personnel within the facility
intended for Manual activation.
Medical Alert Condition operation will initiate the following events:
The piezo sounder ¼ second On, ¼ second Off
The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones, and time/date
Communicate the medical alert condition to the Central Station
Relays programmed for medical alert will be activated
The alarm relay is not activated
Fire Alarm NACs will not activate
SLC NACs (control modules) will activate
Timers are not started
Store event in history buffer
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Each ANN-LED can support up to 10 zones.
Medical alert conditions latch. They can be assigned to software zones.
164
Hazard/Tornado Condition Operation
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010