1.7.9 Legacy ACS Series LED Zone Type Annunciators
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used on
the primary ANN-BUS connector (TB9) due to incompatible serial communication protocols.
Refer to "Guidelines" on page 22 for rules governing the use of various annunciator types.
The legacy ACS Series Annunciators remotely display alarm and trouble status as well as system
status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For
more detailed information, refer to the appropriate annunciator manual. Following is a list of
annunciators which can be used with the MS-9200UDLS.
ACM-16ATF
and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power
LED and a local piezo sounder.
AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs
and 16 yellow trouble LEDs
ACM-32AF
addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It
also has a switch for local piezo silence.
AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs
* In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi-
sory, burglary or trouble signals. Green indicates the presence of power, or an activated output.

LCD-80F/LCD-80FC Remote Fire Annunciator/Indicator

The LCD-80F/LCD-80FC annunciator/Indicator is an 80-character backlit LCD remote fire annun-
ciator/indicator that is capable of displaying English language text. Communications between the
control panel and the annunciator is accomplished over a serial interface employing the EIA-485
communication standard. Up to 32 LCD-80F/LCD-80FC annunciators/indicators may be con-
nected to the EIA-485 circuit. The annunciators/indicators may be powered from the host FACP or
a remote UL listed filtered power supply such as the FCPS Series. For more detailed information,
refer to the LCD-80F and LCD-80FC manuals.

LDM Series Lamp Driver Modules (Graphic Annunciator)

The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F
expander modules, are used to provide an interface to a custom graphic LED annunciator.

Legacy ACM-8RF Relay Control Module

The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. The
ACM-8RF mounts in the lower right corner of the FACP backbox using the ACM-8RF-BRKT
mounting bracket, also allowing space for batteries.
1.8 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS-9200UDLS on-
line:
Install Backbox and Main Circuit Board (refer to "Mounting the Backbox" on page 45)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to "Autoprogram" on page 65)
Resolve Programming Conflicts
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs
*
Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In
*
Product Description
41