Installation

4XTMF
Figure 2.16 4XTMF Connectors to MS-9200UDLS Connectors
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. Relay 3 at TB5 must be programmed as
a supervisory relay.
Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens.
2.9.2 Printer
A serial printer may be connected to TB8 Terminals 1 - 4 on the FACP when TB8 is not being used
for annunciators or a local PC connection. The printer can be used to provide a hard-copy printout
of real-time events, history file and walktest data. Installation the device requires panel program-
ming to allow the FACP to communicate with the device.
A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel
Interface Module. Refer to "ANN-S/PG Serial/Parallel Interface Installation" on page 30 for
installation details. Refer to "ANN-BUS Options" on page 120 for programming information.
CAUTION:
!
DO NOT CONNECT A PRINTER OR PC TO THE MS-9200UDLS FACP IF A GROUND FAULT
(ZERO IMPEDANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE
MAY RESULT. REMOVE ALL POWER (PRIMARY AND SECONDARY) BEFORE INSTALLING OR
REMOVING ANY WIRING.
Installation
Serial printers and PCs require separate primary power. Also required is the serial
PRT/PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-
CABLE to TB8 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector
to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer
or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and
58
TB5
Standoff
NO NC C
J5 & J6 Connectors
FACP main circuit board
POSSIBLE EQUIPMENT DAMAGE
TB6
TB8
TB9
Standoff
+
-
NC NO C
Xmt Rcv Dtr Gnd
B+ A+ B- A- A B
A
B
A
B
Slc Slc Slc Slc Shield
In+ In- Out+ Out-
4XTM
J5
J7
JP3
SW1
PH16
PH15
PRI. PHONE LINE
SEC. PHONE LINE
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Optional Module Installation