Programming
Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop
Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each
addressable device on the loop must have a pair of isolator modules, one on each side.
NOTE on SLC Troubles:If the FACP reports an open fault on an SLC Loop programmed for Style
6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset
button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to
clear the SLC trouble.

Loop Protocol

Loop Protocol refers to the SLC loop mode of operation. Refer to "Wire Requirements" on
page 208 for wire specifications based upon SLC protocol. There are two Loop Protocols available:
CLIP (Classic Loop Interface Protocol) - which is used for the older legacy addressable
devices such as the M300 Series modules and detectors.
LiteSpeed (factory default setting) - used for the 350 Series or newer addressable devices for
quicker response times. Note that the legacy devices can operate only in CLIP mode while the
newer devices are compatible with CLIP and LiteSpeed modes of operation.
Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed
Protocols.

Device Addressing

It is important to note that the MS-9200UDLS addressable device capacity is 99 detectors and 99
control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses
will not function with the MS-9200UDLS.
Note that It is permissible to mix old and new devices on the same loop but the FACP must be set
for CLIP mode when older devices are installed.
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the trouble
condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and
retransmit the trouble condition to the central station if connected.
Banner: This option allows the user to change the top two lines of the LCD display from the
blank factory default readout to a user defined readout when the control panel is in Normal
condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the programming of certain options to Canadian
specifications.
98
Master Programming Level
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010