Section 3: Programming; Programming Data Entry - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below:
Program feature
Permitted in
or option
UL 864? (Y/N)
Trouble Call Limit
Remote Download

3.1 Programming Data Entry

Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the
control panel main circuit board.
The information presented in this section refers to programming the MS-9200UDLS via the
onboard keypad. If an optional computer keyboard is connected to the MS-9200UDLS main circuit
board, the following table describes the keyboard keys which correspond to the onboard keypad
keys.
60

Section 3: Programming

AND OTHER INVOLVED PARTIES
Possible settings
N
Refer to "Trouble Call Limit (Dialer Runaway Prevention)"
on page 136.
Trouble Call Limit = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Y
Refer to "Remote Site Upload/Download" on page 186.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Keypad Keys
1st Event
CLR
ESC
RECALL
*
#
A - Z
0 - 9

(on QZ key)
/
ENTER
ACK/STEP
SILENCE
DRILL
RESET
Computer Keyboard Keys
Home
Delete
Esc
Insert
*
#
A - Z
0 - 9
Space bar
/
Enter
F1
F2
F3
F4
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Settings permitted
in UL 864
Trouble Call Limit =
0 for unlimited
Central Station
trouble calls
Remote Download
Proprietary Yes for
Proprietary system
intended to protect
only contiguous
properties

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents