Programming
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE POINT
Central Station Screen #2
ON BOARD DACT
1=FUTURE USE
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT

3=PRINTER/PC

NO
Option Module Screen
144

Report Style

Pressing 3 while viewing Central Station Screen #2 will cause the Report Style display to toggle
between Point and Zone. Setting the Report Style to Point will program the DACT to report
individual point status to the Central Station. The control panel is capable of monitoring a total of
198 addressable devices. Setting the Report Style to Zone will program the DACT to report zone
status to the Central Station. The control panel is capable of monitoring a total of 99 individual
zones.
NOTES:
1. Detector Address 01 will be reported to the Central Station as Point 01, Detector Address 02
as Point 02, with reports continuing in a similar fashion all the way up to Detector Address 99
which will be reported as Point 99.
2. Module Address 01 will be reported to the Central Station as Point 160, Module Address 02 will
be reported to the Central Station as Point 161, with reports continuing in a similar fashion all the
way up to Module Address 99 which will be reported as Point 258.
Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2 by
the DACT when using an alternate means of secondary transmission path. The factory default
setting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the following
screen to be displayed:
SUPERVISE PHONE LINE
1=PHONE LINE 2
Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone
Line 2 Yes and No.
Printer/PC
A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option
Module Screen will cause the following screen to appear:
1=PRINTER NO SU
2=PRINTER SU
3=PC
Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised
(NO SU) printer. The display will change to the Printer Baud Rate Screen as shown below.
Pressing 2 while viewing the Printer-PC Screen will program the control panel for a supervised
(SU) printer. Printer supervision, when enabled, will typically detect the removal of the printer
cable and will detect when the printer power has been turned off. Depending upon the brand of
printer, other errors such as paper empty or printer off-line may be detected.
YES
Panel ID Screen
PRINTER-PC
YES
NO
Printer-PC Screen
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010