Nac (Notification Appliance Circuit) - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Master Programming Level
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
RANGE 00-23
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss
reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will
return to AC Loss Delay Screen #1.
Upon the loss of AC power at the control panel, relays programmed for 'AC Loss' will
NOTE:
transfer immediately, regardless of the AC Loss Delay setting. If no trouble exists at the panel
other than AC Loss, the System Trouble relay will delay its activation for the duration of the AC
Loss Delay setting.

NAC (Notification Appliance Circuit)

The options for the NACs on the control panel main circuit board can be configure by pressing 2
while viewing System Setup Screen #2. The following screens will be displayed:
1=NAC 1
2=NAC 2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.
AC LOSS DELAY
AC Loss Delay Screen #2
NACS
3=NAC 3
4=NAC 4
NAC Selection Screen
Programming
105