Programming
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
136
Central Station
Central Station programming configures the control panel DACT for contacting the central station.
Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be
displayed:
1=REPORTING DISABLED
2=REPORT
3=CALL LIMIT
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing
Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will
toggle the display between Reporting Disabled and Reporting Enabled.
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a
programmed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate
limit counters keep track of each unique type of trouble. Note that the number of phone line
(communication) faults called to the Central Station are not limited by this feature. No subsequent
restoral message is sent to the Central Station(s) for a particular trouble whose call limit has been
reached. Local DACT annunciation will still track the particular trouble and restoral.
CENTRAL STATION
BACKUP
Central Station Screen #1
CENTRAL STATION
Central Station Screen #2
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Master Programming Level