Programming
The following screens will be displayed for each selection:
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.
NOTE: The programming for NAC 1 will determine the operation of the remote power supply sync.
106
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC #
1=AUTO SILENCE
2=CODING
TEMPORAL
NAC Screen #2
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED
NAC Screen #3
NAC #
1=SYNC TYPE
NAC Screen #4
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Master Programming Level
YES
BELL
YES
00
NO
S