Fire-Lite MS-9200UDLS Manual page 222

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Canadian Application
Notes:
1. The CRF-300 and the MMF-300
must be mapped to the same zone
which is programmed for supervisory
operation.
2. No other device can be mapped to
that supervisory zone.
3. Wire gauge must be 18AWG
minimum.
+
(to remote station receiver)
-
CRF-300*
Terminal IDs
T10 - Comm2
T1 - SLC -
T9 - N.C. 2
T2 - SLC +
T8 - N.O. 2
T7 - Comm1
T6 - N.C. 1
T5 - N.O. 1
Figure I.3 Alternate Transmission for Supervisory Signals
222
T11
T10
T1
MMF-300*
T2
T9
T8
T3
-
T4
T7
T6
T5
+
T11
T10
CRF-300*
T1
T2
T9
T8
T3
T4
T7
T6
T5
violet
red (+)
black (-)
violet
EOLR-1
*If the SLC device does not match the one in this figure, refer to the SLC manual
appendix, which contains wiring conversion charts for type V and type H modules.
-
B-
+
B+
-
+
-
+

47K
resistor
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
TB10-
SLC Loop
Output
Non-resettable
Aux Power
24 VDC- TB1
FACP