Product Description
The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms)
Maximum Wire Length (feet)
(6,000 feet maximum)
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:

Wiring Distance Calculation Example:

Suppose a system is configured with the following ANN-BUS modules:
3 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
The total worst case current is calculated as follows:
ANN-80 Current Draw
ANN-S/PG Current Draw
Total Worst Case Current Draw
Using this value and referring to the Wiring Distance Table 1.1 on page 23, it can be found that the
available options are:
926 feet maximum using 22 Gauge wire
2,344 feet maximum using 18 Gauge wire
3,731 feet maximum using 16 Gauge wire
5,906 feet maximum using 14 Gauge wire
24
6.0 Volts
=
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
=
Rpu
Wire Gauge
22
18
16
14
Wire Gauge
18
16
14
12
= 3 X 0.040 amps
= 1 X.0.040 amps
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Ohms per 1,000 feet (Rpu)
16.2
6.4
4.02
2.54
Maximum Wire Length
312 feet
497 feet
787 feet
1,250 feet
= 0.120 amps
= 0.040 amps
= 0.160 amps