System Programming
System programming is entered directly by password or is automatically entered after reconfiguring the control
panel.
After entering the system programming password (123-1232), the green PASSWORD ACCEPT LED and the
yellow PROGRAM/SERVICE LED will illuminate. System programming is performed sequentially. The first
function to be programmed is WATERFLOW.
Waterflow Operation
Notification Appliance Circuits, and other out-
puts activated in response to an alarm on a
waterflow initiating circuit, cannot be silenced
by the SIGNAL SILENCE switch.
Programming Waterflow Circuits
The WATERFLOW LED will flash to indicate
the control panel is ready to be programmed for
waterflow circuits.
A flashing yellow initiating circuit LED serves
as the pointer. It shows the programmer what
circuit is being programmed at that time. Press
the STATE CHANGE switch to select or dese-
lect this circuit for waterflow alarm. The red
LED on that circuit will illuminate when that
circuit has been selected. Pressing the POINT
SELECT A switch advances the pointer to the
next initiating circuit. Pressing the POINT
SELECT B switch moves the pointer to the
previous initiating circuit.
When all waterflow circuits have been se-
lected, press the FUNCTION SELECT switch
to store the WATERFLOW programming infor-
mation and advance programming to the next
function – SUPERVISORY.
Supervisory Operation
Activation of a device on a circuit programmed
for supervisory will light the supervisory LED.
System trouble LED and system trouble out-
puts will not be activated. Supervisory circuits
can map to controlled outputs and can detect
the difference between a "normally open" su-
pervisory switch and a break in the field wiring.
Programming Supervisory Circuits
The Supervisory LED will illuminate steadily on the CPU. The pointer LED will be at the first initiating circuit. Use
the STATE CHANGE switch to select or deselect that circuit for supervisory. The POINT SELECT switches move
the pointer to the other initiating circuits. When all Supervisory circuits have been programmed, press the
FUNCTION SELECT switch to store the programming information and advance programming to the next function
— SILENCEABLE.
Note: Circuits programmed for both Supervisory and Non-Alarm performs special functions. Refer to "Remote
Command Inputs" in Section Six.
48
S200 15032 Rev C 02/22/96 P/N 15032:C
PROGRAMMING
PROGRAMMING
PROGRAMMING
PROGRAMMING
PROGRAMMING
REMOVE THIS CARD AFTER
PROGRAMMING
F ENTER PASSWORD
S PASSWORD/ACCEPTED
F WALK TEST
S RECONFIGURE
F PRESS ENTER
S PROGRAM/SERVICE
F WATERFLOW
S SUPERVISORY
F SILENCEABLE
S CODED CIRCUIT
F CODE TYPE
S VERIFIED/PAS
F NON ALARM INPUTS
S ANNUNCIATOR INSTALL
F SILENCE INHIBIT
S I/O MAP
FUNCTION
FUNCTION
1
SELECT
SELECT
POINT A
2
POINT A
SELECT
POINT B
SELECT
3
(ESCAPE)
E
E
N
N
STATE
T
T
STATE
E
E
CHANGE
R
CHANGE
R
Code Type
Temporal
March Time
Annunciators
None
Annun
Annun. Mode
Output
Control
Silence Inhibit
None
30 sec
60 sec
5 min