System Programming

System programming may be entered directly by password or is automatically entered after reconfiguring the
panel.
After entering the system programming password (123-1232), the green PASSWORD ACCEPT LED and the
yellow PROGRAM/SERVICE LED will illuminate. Programming of the system is performed sequentially. The first
function to be programmed is WATERFLOW.
Waterflow Operation
Notification Appliance Circuits and other out-
puts that are activated in response to an alarm
on a waterflow initiating circuit cannot be si-
lenced by the SIGNAL SILENCE switch.
Programming Waterflow Circuits
The WATERFLOW LED will flash to indicate the
control panel is ready to be programmed for
waterflow circuits.
A flashing yellow initiating circuit LED serves as
the pointer.
It shows the programmer what
circuit is being programmed at that time. Press
the STATE CHANGE switch to select or dese-
lect this circuit for waterflow alarm. The red LED
on that circuit will illuminate when that circuit has
been selected. Pressing the POINT SELECT A
switch advances the pointer to the next initiating
circuit. Pressing the POINT SELECT B switch
moves the pointer to the previous initiating cir-
cuit.
When all waterflow circuits have been selected,
press the FUNCTION SELECT switch to store
the WATERFLOW programming information
and advance programming to the next function
— SUPERVISORY.
Supervisory Operation
Activation of a device on a circuit programmed
for supervisory will light the supervisory LED.
The system trouble LED and the system trouble outputs will not be activated. Supervisory circuits can be mapped
to controlled outputs. Circuits can detect the difference between the normally open supervisory switch and a break
in the field wiring.
Programming Supervisory Circuits
The Supervisory LED will illuminate steadily on the CPU. The pointer LED will be at the first initiating circuit. Use
the STATE CHANGE switch to select or deselect that circuit for supervisory. The POINT SELECT switches move
the pointer to the other initiating circuits. When all Supervisory circuits have been programmed, press the
FUNCTION SELECT switch to store the programming information and advance programming to the next function
— SILENCEABLE.
Note: Circuit programmed for both supervisory and non-alarm performs special functions. See Remote Command
Inputs.
47
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1