Troubleshooting Tables
No.
Problem
33
Rotation is
reversed.
34
35
36
37
The positioning
completed signal is
not output or is
delayed. (The next
operation cannot be
started.)
38
39
40
314
Probable causes
The Servo Drive is set for
reverse rotation.
The CW and CCW pulse out-
put signals are reversed.
During an origin search the
origin proximity sensor polar-
ity does not match the param-
eter setting (in the PCU) for
the origin proximity input
polarity.
During an origin search, the
origin proximity input wiring is
faulty.
The Servo Drive's in-position
width set in the PCU parame-
ters is too narrow, and the
axis is not in the in-position
range. (If it is not in the in-
position range, the next oper-
ation cannot be started
because the preceding opera-
tion is not completed.)
The wiring for the Servo
Drive's positioning completed
signal is faulty.
The servo speed reference is
incorrect.
The axis is not in the in-posi-
tion range due to external
pressure applied when posi-
tioning stopped.
Items to check
If JOG operation is executed and
the direction is the opposite of
the JOG direction, check
whether the Servo Drive is set
for reverse rotation. Also, check
that the feedback signals (A-
phase/B-phase) are not reversed
and that operation is not set for
reverse in the parameters.
Check the wiring for the CW and
CCW pulse output signals.
Check the parameter setting and
the sensor polarity.
Check the that the origin proxim-
ity input signal in the operating
memory area is turning ON and
OFF.
---
Check the that the positioning
completed signal in the operat-
ing memory area is turning ON
and OFF.
---
Using the Servo Drive's monitor-
ing functions, monitor the error
counter and check whether the
axis is in the in-position range.
Section 11-1
Remedy
Correct the setting for the
direction of Servo Drive
rotation.
Correct the wiring.
Correct the parameter
setting.
Correct the origin proxim-
ity input wiring.
Increase the in-position
width set in the PCU
parameters.
Correct the wiring for the
positioning completed
signal.
Adjust the Servo Drive's
gain.
If positioning is stopped
outside of the in-position
range due to external
pressure, it is possible to
forcibly position in the in-
position range using error
counter reset output.
Doing this, however, will
result in an unestablished
origin state and so it is
necessary to re-establish
the origin by repeating
origin search or by per-
forming present position
preset.