Transferring and Saving Data
5-1-3

Data that Can be Saved and/or Transferred

5-1-4

Data Addresses

116
4. There is a limit on the number of times you can read something using the
flash memory. Set this so that up to 100,000 data saving operations can be
performed.
All the following data used by the PCU can be read, written, and saved to the
flash memory. The timing with which transferred data is enabled varies
according to the type of data. For details on the enable timing of the axis
parameters, refer to 4-4 Axis Parameter Area. Data other axis parameters
(e.g., positioning sequences and positions) will be enabled immediately after it
is transferred.
Note
The following types of data can be saved together in the flash memory.
• Axis parameters (see note)
• Positioning sequences
• Speeds
• Positions
• Acceleration times
• Deceleration times
• Dwell times
• Zones
Note
When the power is turned ON or when the PCU is restarted, a choice is avail-
able by using the axis parameter designation setting in the DM Area common
parameters (refer to 4-3 Common Parameter Area) between sending the axis
parameters automatically from the DM Area to the PCU or using the axis
parameters saved in the PCU.
PLC
*
*Note The last word address varies
with the model.
Each data item has its own address in the PCU, and this address is used to
identify the write destination and read source when data is transferred. One
word (16 bits) is used to designate each address. It is not possible to transfer
data extending across axis parameters and data for the X, Y, Z and U axes.
Note
When transferring an item of data, transfer the data for all the words allocated
to that item. For details of the word configurations for data, refer to SECTION
4 Data Areas.
PCU
Internal
memory
At power on
Axis
or restart
param-
eters
When axis
parameter
designation
(m+2) = 01
When power is turned ON or upon restarting
When axis parameter designation (m+2) = 00
Section 5-1
Flash
memory
Axis
param-
eters