Nortel DMS-100 Series Maintenance Manual page 463

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

SysB
PM
0
STAR
0
STAR REM1 00 0
ISTb
Unit 0:
ISTb
Unit 1:
ManB
Drwr:
11 11 11 11 11 22 22 22 22 22 33 33 33 Pref
01 23 45 67 89 01 23 45 67 89 01 23 45 67 89 01 23 45 Stby
.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
5
Determine the unit associated with the NTTR60 card to be replaced by using
the following table.
If STAR unit
0
1
6
Check the state of the STAR units.
If the STAR units are
OFFL or SysB
One unit is InSv or ISTb
the other unit is ISTB
SysB
7
To switch ringing generator activity to the good NTTR60 card, type
>SWRG UNIT unit_no
and press the Enter key.
where
unit_no
is the STAR unit (0 or 1) aligned to the faulty RG
Note: If necessary, repeat this step until both units of the STAR are on the
good RG.
If the SWRG command
passes
fails
8
To busy the STAR unit associated with the faulty RG, type
>BSY UNIT unit_no
and press the Enter key.
Star Remote System card replacement procedures
ManB
OffL
0
2
0
2
Links_OOS: CSide 0 PSide 0 UMP OOS:0
/RG: 0
/RG: 0
DMS-100 Family NA100 Star Remote System XPM15 and up
in a STAR
CBsy
ISTb
0
1
0
1
Do RG card
0 in slot 1
1 in slot 22
Do
step 8
step 7
or
Do
step 8
step 21
12-115
NTTR60
(continued)
InSv
12
9
RG:
0 InSv
1 InSv