Nortel DMS-100 Series Maintenance Manual page 333

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

and pressing the Enter key.
where
unit_no
is the STAR unit (0 or 1) associated with the new RG
Example of a MAP display:
STAR REM1 14 1 Unit 1 SWRG Passed
If the SWRG command
passed, and RG activity must be
switched for the other unit
passed, and RG activity is
acceptable for both units
failed
13
Repeat step 12 for the other STAR unit.
14
Repeat steps 7 through step 13 for the other STAR unit.
15
Go to the "Star Remote Hub card replacement procedures" in this manual.
Begin by replacing the first card on the list. When you have finished with the
card replacement procedures, go to step 11 of this procedure.
16
Obtain further assistance in clearing this alarm by contacting personnel
responsible for higher level support.
17
You have successfully completed this procedure. If there are other alarms
displayed, reference the appropriate alarm clearing procedures for the
indicated alarms in this manual.
Star Remote System alarm clearing procedures
DMS-100 Family NA100 Star Remote System XPM15 and up
PM STAR RG
critical
Do
step 13
step 17
step 16
11-67
(end)