Nortel DMS-100 Series Maintenance Manual page 343

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

where
unit_no
is the STAR unit (0 or 1) assigned to the new RG
Example of a MAP display:
STAR REM1 14 0 InSv Links OOS: Cside 0 Pside 0
Unit 0: InSv
Unit 1: InSv
Drwr:
11 11 11 11 11 22 22 22 22 22 33 33 33 Pref 0 InSv
01 23 45 67 89 01 23 45 67 89 01 23 45 67 89 01 23 45 Stby 1 InSv
.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
Note: Repeat this step until both units of the STAR are on the preferred
RG.
If the SWRG command
passes
failes
18
Go to the appropriate procedure in the "Star Remote System card
replacement procedures" in this manual. When you have finished with the
card replacement procedures, go to step 13 of this procedure.
19
Get additional help in clearing this alarm by contacting the personnel
responsible for higher level support.
20
You have correctly completed this procedure. If there are other alarms
displayed, reference the appropriate alarm clearing procedures for the
indicated alarms in this manual.
Star Remote System alarm clearing procedures
/RG:0
/RG:0
DMS-100 Family NA100 Star Remote System XPM15 and up
PM STAR RG
major, minor
RG
Do
step 20
step 19
11-77
(end)