Nortel DMS-100 Series Maintenance Manual page 313

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

link_no
is the number of a faulty P-side link busied in step 13
If RTS
passed and no other links are
SysB
passed but other links are SysB
failed
16
Determine if the problem is a drawer with faults. A drawer with faults is
indicated by letters appearing under the line subgroup numbers associated
with a physical drawer.
Example of a MAP response:
STAR REM1 00 0
Unit 0:
InSv
Unit 1:
InSv
Drwr
01 23 45 67 89 01 23 45 67 89 01 23 45 67 89 01 23 45
.. .. .. .. .. .. .. .. SS .. .. .. .. .. .. .. .. ..
If problem indicated is
a drawer with faults
not a drawer with faults
17
Determine if the line drawer with faults is in the Hub or is a remote line drawer
(RLD).
Note: At the MAP display, line drawers in reverse video represent an RLD.
If the line drawer with faults is
in the Star Hub
an RLD
Star Remote System alarm clearing procedures
CAUTION
Failing to allow sufficient time may cause false alarm indication.
Allow 3 to 5 minutes for the system to clear the alarm before
proceeding to the next step.
ISTb
Links_OOS: CSide 0 PSide 0 UMP OOS:0
/RG: 0
/RG: 0
11 11 11 11 11 22 22 22 22 22 33 33 33
DMS-100 Family NA100 Star Remote System XPM15 and up
minor
Do
step 61
step 13
step 59
Do
step 17
step 49
Do
step 18
step 21
11-47
PM STAR
(continued)