11-50 Star Remote System alarm clearing procedures
PM STAR
minor
(continued)
24
25
26
27
28
297-8353-550 Standard 05.01 March 2001
If the fault indicated is
load file erased from a firmware
bank
link busy
Bd channel busy
DS-1 static data mismatch
none of the above
To busy the RLD, type
>BSY DRWR
and press the Enter key.
To return the RLD to service, type
>RTS DRWR
and press the Enter key.
If RTS
passed
failed, and a card list is produced step 52
failed, but no card list is pro-
duced
From office records, determine the correct load name that should be entered
and running in the RLD.
To determine the load file entered in table LCMDRINV for the posted RLD,
type
>QUERYRLD
and press the Enter key.
If the load file entered in table
LCMDRINV and office records
match
do not match
To display the load file in the RLD, type
>QUERYRLD CNTRS
Do
step 36
step 39
step 43
step 24
step 45
Do
step 61
step 59
Do
step 28
step 29