User Constants Setable in Quick Programming Mode

The minimum user constants required for Inverter operation can be monitored and set in quick programming
mode. The user constants displayed in quick programming mode are listed in the following table. These, and
all other user constants, are also displayed in advanced programming mode.
Con-
stant
Number
A1-00
b1-01
b1-02
b1-03
b1-04
b4-01
b5-01
-4
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Used to select the language displayed on
the Digital Operator JVOP-160 only.
0: English
1: Japanese
Language selec-
2: German
tion for Digital
3: French
Operator display
4: Italian
5: Spanish
6: Portuguese
This constant is not changed by the initial-
ize operation.
Sets the frequency reference input
method.
Reference
0: Digital Operator
source selection
1: Control circuit terminal (analog input)
2: MEMOBUS communications
3: Option Card
Sets the run command input method
0: Digital Operator
RUN command
1: Control circuit terminal (digital multi-
source selection
function inputs)
2: MEMOBUS communications
3: Option Card
Select stopping method when stop com-
mand is input.
0: Deceleration to stop
1: Coast to stop
Stopping
2: DC braking stop (Stops faster than
method selection
coast to stop, without regenerative
operation.)
3: Coast to stop with timer (Run
commands are disregarded during
deceleration time.)
0: Reverse enabled
1: Reverse disabled
Prohibition of
2: Output Phase Rotation (both rotational
reverse opera-
directions are enabled)
tion
3: Output Phase Rotation with Reverse
prohibited.
Sets the timer function output ON-delay
time (dead time) for the timer function
Timer function
input, in 1-second units.
ON-delay time
Enabled when a timer function is set in
H1-
and H2-
0: Disabled
PI control mode
1: Enabled
selection
3: PI control enabled (frequency reference
+ PI output)
Setting
Description
Range
0 to 6
0 to 3
0 to 3
0 to 3
0 to 3
0.0 to
3000.0
.
0, 1, 3
MEMO-
Change
Access
BUS
during
Factory
Setting
Level
Regis-
Opera-
tion
ter
0
Yes
A
100H
1
No
Q
180H
1
No
Q
181H
0
No
Q
182H
0
No
A
183H
0.0 s
No
A
1A3H
0
No
A
1A5H