Con-
stant
Name
Number
b5-21
Sleep Function Selection
b5-22
Snooze Level
b5-23
Snooze Delay Time
b5-24
Wake-Up Level
b5-25
Setpoint Boost
b5-26
Maximum Boost Time
b5-27
Snooze feedback
PI Feedback Square Root Opera-
b5-28
tion
b5-29
PI Feedback Square Root Gain
b5-30
PI Output Monitor Square Root
Monitor Items (U1-
)
Constant
Name
Number
U1-24
PI feedback value
U1-36
PI input volume
U1-37
PI output volume
U1-38
PI setpoint
U1-53
PI feedback 2
Multi-Function Contact Inputs (H1-01 to H1-05)
Set
Value
19
PI control disable (ON: PI control disabled)
30
PI control integral reset (reset when reset command is input or when stopped during PI control)
31
PI control integral hold (ON: Integral hold)
34
PI soft starter
35
PI input characteristics switch
Multi-Function Analog Input (H3-09)
Set
Value
B
PI feedback
C
PI target value
16
PI feedback 2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Sets the operation method of the PI sleep function
0: Output frequency before Softstarter (SFS)
1: Frequency reference/PI target
2: Snooze
Sets the frequency level at which the snooze operation
starts as percentage of the max. output frequency.
Sets a delay timer for the snooze function
Sets the feedback level at which the inverter wakes up from
snooze operation.
Sets the PI setpoint boost when the snooze mode is acti-
vated. If it is reached once the output will be switched off.
The value is set as percentage of the PI setpoint.
Sets the maximum time the boost operation is performed.
PI Snooze function will only be activated when the feed-
back value is above this parameter setting.
The value is set as percentage of the PI setpoint.
Enables or disables the square root operation for the PI
feedback value.
0: Disabled
1: Enabled
Sets the gain for the feedback when square root operation is
enabled.
Selects whether the PI output monitor is shown as square
root value or not.
0: Disable
1: Enable
Description
Monitors the feedback value when PI control is used. 10 V: 100% feedback
PI input volume
PI control output
PI setpoint
Monitors the feedback 2 value when Differential PI is
selected.
Function
Function
Max. output frequency
Max. output frequency
Max. output frequency
Individual Functions
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
1 to 2
0
No
0 to 100%
0
Yes
0 to 3600
0 s
No
s
0 to 100 %
0
No
0 to 100%
0
No
0 to 3600
0 s
No
s
0 to 100%
60%
No
0 or 1
0
No
0 to 2.00
1.00
No
0 or 1
0
No
Output Signal Level During
Multi-Function Analog Output
0.01%
10 V: 100% PI input
0.01%
10 V: 100% PI output
0.01%
10 V: 100% PI target
0.01%
10 V: 100% PI feedback
0.01%
A
A
A
A
A
A
A
A
A
A
Min.
Unit
85
6-