Speed Limit (Frequency Reference Limit Function)

This section explains how to limit the motor speed.

Limiting Maximum Output Frequency

If you do not want the motor to rotate above a given frequency, use constant d2-01.
Set the upper limit value of the frequency reference as a percentage, taking E1-04 (Maximum Output Fre-
quency) to be 100%.
Related Constants
Con-
stant
Name
Number
d2-01
Frequency reference upper limit

Limiting Minimum Frequency

If you do not want the motor to rotate below a given frequency, use constants d2-02 or d2-03.
There are two methods of limiting the minimum frequency, as follows:
Adjust the minimum level for all frequencies.
Adjust the minimum level for the master speed frequency (i.e., the lower levels of the jog frequency,
multi-step speed frequency, and auxiliary frequency will not be adjusted).
Related Constants
Con-
stant
Name
Number
d2-02
Frequency reference lower limit
Master speed reference lower
d2-03
limit
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Speed Limit (Frequency Reference Limit Function)

Description
Set the output frequency upper limit, taking the max. out-
put frequency to be 100%.
Description
Set the output frequency lower limit, taking the base refer-
ence to be 100%.
Set the master speed reference lower limit, taking the max.
output frequency to be 100%.
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0.0 to
100.0%
No
A
110.0
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0.0 to
0.0%
No
A
110.0
0.0 to
0.0%
No
A
110.0
25
6-