YASKAWA Varispeed E7 Instruction Manual And Parameter Description page 240

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Con-
stant
Name
Number
Cumulative operation time selec-
o2-08
tion
o2-09
Initialize Mode
o2-10
Fan operation time setting
o2-12
Fault trace initialize
o2-14
Energy monitor initialize
o2-15
HAND key function selection
Monitor Selection (o1-01)
Using constant o1-01 the third monitor item that is displayed in drive mode can be selected. This function has
no effect on the optional LCD-operator (JVOP-160).
Monitor Display when the Power Supply is Turned ON (o1-02)
Using constant o1-02 the monitor item (U1-
power supply is turned ON can be selected.
Changing Frequency Reference and Display Units o1-03)
Set the Digital Operator frequency reference and display units using constant o1-03. The setting in o1-03 will
affect the display units of the following monitor items:
U1-01 (Frequency Reference)
U1-02 (Output Frequency)
U1-05 (Motor Speed)
U1-20 (Output Frequency after Soft Start)
d1-01 to d1-04 (Frequency references)
Disabling the LOCAL/REMOTE Key (o2-01)
Set o2-01 to 0 to disable the LOCAL/REMOTE Key on the Digital Operator.
If the key is disabled, it cannot be used anymore to switch over the frequency reference source or the RUN
command source between LOCAL and REMOTE.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
0: Cumulative time when the Inverter power is on. (All
time while the Inverter power is on is accumulated.)
1: Cumulative Inverter run time. (Only Inverter output
time is accumulated.)
2: Europe
5: PV-E Spec
Set the initial value of the fan operation time using hour
units.
The operation time accumulates from the set value.
0: Disable
1: Initialize (= zero clear) after setting "1" o2-12 will be
returned to "0"
Resets the monitor parameter U1-29 and U1-30 back to
zero.
0: No change
1: Reset to zero
If set to 0 the HAND button on the digital operator is dis-
abled and the drive will not enter the HAND mode and
start to run when the HAND button is pressed.
0: HAND button disabled
1: HAND button enabled
) that is to be displayed on the Digital Operator when the
Digital Operator Functions
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 or 1
0
No
A
2 or 5
2
No
A
0 to
0
No
A
65535
0 or 1
0
No
A
0 or 1
0
No
A
0 or 1
1
No
A
103
6-

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Cimr-e7c